|
September 24, 2004 Backflow Assembly Testers (BAT) are allowed to use references during BAT Certification and Professional Growth Examinations through December 2004. The Department of Health, Office of Drinking Water, is pilot-testing the use of two references during the exam: Backflow Prevention Assemblies Field Test Procedure Approved for Use in Washington State and the short version of these procedures. These are being made available at each test-station for examinees to use during the examinations. The Department of Health will review the results of the pilot test early next year to determine whether or not to continue their use. January
1, 2004 began a new professional growth reporting period for Washington
State Certified Backflow Assembly Testers.
All certified BAT’s needing
to satisfy their BAT professional growth requirement during this
reporting period must take and pass the Washington State Department
of Health Backflow Assembly Tester Professional Growth Examination by
December 31, 2006. To pass the professional growth exam, the BAT must demonstrate ability to correctly test the RPBA, DCVA, PVBA, and SVBA. They must also demonstrate knowledge and skill of troubleshooting backflow prevention assemblies by correctly diagnosing a simulated failure condition on the RPBA, DCVA, and PVBA. The test procedures have been clarified and Backflow Assembly Testers should be aware of these modifications to procedures which will help prevent problems during testing. The
RPBA test procedures were modified to prevent the differential pressure
relief valve from opening prior to the test of the relief valve. These modifications do not affect the actual
testing of the RPBA but rather aid in preventing the accidental and
premature opening of the differential pressure relief valve before testing. The following flushing process will prevent premature
opening of the relief valve: Open
and leave open TC #4, TC #3, TC #2, & TC #1, then Close
TC #1, TC #2, TC #3 & TC #4 in sequence. The process for purging air from the RPBA was also
modified as follows: Slowly
open TC #3 and the low side bleed valve, leave open. Slowly
open TC #2 and the high side bleed valve, leave open. Isolate
the assembly by closing SOV #2, then Close
the high side bleed valve, and After the gauge has reached the upper limits, close the low side bleed valve. The
test procedures for the DCVA, PVBA and SVBA have
been clarified and require that the test kit be elevated to the correct
level prior to isolating SOV #1 when testing each component. This procedure
is currently a requirement of the Backflow Prevention Assemblies
Field Test Procedure Approved for Use in Washington State. The
SVBA test procedures have been simplified by eliminating repeated
steps to test the CV. This modification allows both the Check Valve
and the Air Inlet Valve to be evaluated with one test. To
test the SVBA 1. Notify,
identify, inspect, and observe 2.
Remove
canopy, flush the test cock and the vent valve
3. Connect
high side hose of test kit to test cock (end of compensating valve) 4. Purge by: Opening the test cock Open and close high side bleed valve on the test kit 5.
Isolate
by: Closing shut off valve #2 Elevating test kit at same centerline of the assembly
and Closing shut off valve #1 6.
Test
the Check Valve Slowly open (remove) SVBA vent valve (screw) Wait for the flow of water to stop and for the needle on the gauge
to stabilize Record psid shown on test kit gauge NOTE: If the air
inlet valve opens at this time, record the gauge reading when it opens
as the opening of the air inlet valve & report that the check valve
leaks. 7.
Test
the Air Inlet Valve Operations NOTE: The test kit must be continued to be held at same elevation as the assembly. Slowly open high bleed valve (maximum ¼ turn) Record psid shown on test kit gauge at time the air inlet
valve opens Continue opening high bleed valve gauge reading is 0.0 psid Observe that the air inlet valve is fully open 8.
Return
to service Close SVBA vent valve Close test cock Replace the canopy Slowly open shut off valve #1 Slowly open shut off valve #2 Remove all test equipment Notify owner Fill out test report Either
the modified procedures or the procedures used during the last professional
growth reporting period may be used for the BAT Certification and the
BAT Professional Growth Examinations.
David Kingsley, BAT Certification and Professional Growth Program Manager Michael Patten, BAT Examination Proctor |